Analysis

A flat cold plate can still make a poor thermal joint

A 40 µm depression over a processor can put more interface material exactly where the heat flux is highest. Tightening the tolerance across the whole plate may leave that joint little better off.
The nickel-plated copper cold plate from a Heatkiller IV GPU water block.

A cold plate can meet a 25 µm flatness requirement across its mounting face and still leave a gap above the hottest part of a processor. Which area was inspected, how the plate was clamped and whether the drawing specified a surface finish all affect what that inspection says about the assembled joint. In its guidance for direct-to-chip cooling, manufacturing supplier MES recommends specifying the part of the face through which the heat actually enters.

A smooth depression and a set of machining marks pose different problems. The depression changes the thickness of the thermal interface material across the die; the marks can leave microscopic pockets even where the two faces appear to sit squarely together. Contact pressure helps the material conform to the surfaces, so inspecting a free plate measures a different condition from bolting it to a package. As Brad Layne, engineering manager at MES, puts it: “A cold plate can pass a flatness check and still add thermal resistance if surface finish was never specified.”

Take the 40 µm depression in MES’s example. To isolate its effect, suppose the extra gap is filled with a material of thermal conductivity 4 W/(m·K) and the local heat flux is 20 W/cm², or 200,000 W/m². For heat flowing straight through that layer, the additional temperature drop is flux multiplied by thickness and divided by conductivity: 200,000 × 0.000040 ÷ 4 = 2°C. The same depression over an area carrying half the heat flux gives 1°C on those assumptions. A profile of the die footprint would distinguish those two regions; a single flatness value for the whole plate would not.

That 2°C belongs to the extra layer of interface material. To turn it into a junction temperature would require the heat spreading in the package, the resistance where the material touches each face and the shape the plate takes under load. Eaton treats surface form, roughness, pressure and filler as distinct contributions: changing the grease or the clamp can alter the joint without changing its measured flatness.

There is a cost to choosing the wrong tolerance. MES says a move from 25 µm to 15 µm can take a face out of precision milling and into grinding or a dedicated fly-cutting operation. Brazing can then release residual stress and distort the machined face. For a brazed plate, specifying when the final face is cut and inspected can be more valuable than tightening an intermediate machining tolerance.

One way to decide whether the extra operation earns its cost is to map the finished faces over the processor footprint, then compare them under the same mounting load with the same interface material. Holding heat input, coolant temperature and flow fixed allows the measured temperature drop across the joint to be compared with the position of the worst gap. A tighter machining call-out then has an identifiable target: the region where reducing the gap actually lowered temperature under load.

Sources: MES: supplier-issued drawing guidance; Eaton: contact thermal resistance.

Continue reading