TEB interviews Ampt on how its 800 V DC converter handles GPU load spikes

Ampt’s Dr. Gustavo Uicich and Steve Reed explain what was measured in the first millisecond and how a battery can take short bursts of demand off the grid connection.
Illustrative photograph of a data centre aisle lined with server racks

Illustrative image: Brett Sayles on Pexels

When a rack of GPUs changes workload, its demand for current can jump before the supply has caught up. Ampt’s design puts a battery on the site’s shared DC bus so the rack can draw that extra power while the upstream supply sees steadier demand. In the test Ampt describes, the converter’s output current took under a millisecond to rise after a voltage disturbance.

The Electronics Brief asked Dr. Gustavo Uicich, Ampt’s Director of Hardware Engineering, and Steve Reed, Product Manager at Ampt, what that figure measures, how the battery and capacitors share the load and what the pilot tells them so far. Their written answers are jointly attributed.

On the grid side, a medium-voltage transformer and power conversion system (PCS) feed the shared DC bus. The bus runs between 1,100 V and 1,500 V as the battery’s state of charge changes. Ampt’s converter takes that varying input and supplies regulated 800 V DC to the rack. Each 2U module is rated at 80 kW, or 100 A at 800 V, and modules can run in parallel for larger loads.

The Open Compute Project is working with Google, Microsoft and NVIDIA on common 800 V DC requirements for denser AI racks. Raising the distribution voltage reduces the current needed to carry the same power. The rack supply still has to cope with sudden changes in demand, which is where Ampt’s battery and converter come in.

The interview

What does the sub-millisecond response measure? Is it the time to detect a load change, start correcting it, or bring the output voltage back within tolerance? What load step and voltage limits did you use in testing?

Ampt

The sub-millisecond response refers to the converter’s output current rise time immediately following the inception of a disturbance on the output voltage, aimed to correct the deviation from the voltage setpoint. The converter performed zero to full load with the 800 V bus held within the +5%/−15% target of the OCP.

Where does the converter sit in the power chain? Could you share a block diagram showing how the grid connection, battery, shared DC bus and GPU racks are connected?

Ampt

The converter sits in front of the GPU. See attached architecture.

A battery-backed DC bus feeds the Ampt converter, which supplies an 800 V DC GPU rack with a capacitor bank.
The battery feeds a shared DC bus at 1,100 V to 1,500 V. Ampt’s converter regulates the feed to the GPU rack at 800 V DC. Image supplied by Ampt.

Which load changes are handled by the battery, and which by capacitors? What does that division mean for battery sizing and cycling?

Ampt

The battery, battery converter, and capacitor banks work together to handle the load changes. The battery provides the energy most of the time. The capacitors are sized to manage fast transient voltages during switching on the order of <1 ms.

The battery system is intended to be the main energy reservoir in the system, preventing the MV front end and hence, the grid, from seeing a fluctuating power demand, which would otherwise force the power station to be overdesigned (MV-transformer/SST/Switchgear/Rectifier) based on the peak consumption instead of the average power drawn by the data center. For Ampt’s converter to be able to react to load changes in one port within a millisecond, there should be energy readily available in the other port to be transferred. However, the relatively slow electrochemical time-response of any battery system requires a capacitor bank placed in parallel, to supply current during the transient and stabilise the input as a voltage source.

On the load side, there will still be capacitors between the battery converter and the GPU to handle transients that are faster than the response time of the battery converter, although those capacitors may be substantially minimized. Other longer duration storage, such as UPS, may be avoided or reduced in favor of using the batteries on the shared DC bus in the attached diagram.

Could you give a worked example of how much a site could reduce its peak grid draw, including the assumed load profile, battery size and how long it could sustain that reduction?

Ampt

The PCS needs only to provide the average power over the cycling time, so the reduction is related to the load profile and duration. Using the pilot data as an example, the load was switching roughly twice per second. For roughly half a second the GPU is taking no power, and for roughly half a second the GPU is taking full power. The PCS has only to provide the average, or half power to maintain battery SOC. This state can exist indefinitely unless the load profile changes, whereas the PCS can ramp to the new average power value.

The durations in Ampt’s written answer imply one full pulse per second. Its chart shows roughly two. We’ve asked Ampt to confirm how long the load spent at each level.

What have the pilots demonstrated so far, and what still needs validating before general availability? Is there a measured result you can share for publication?

Ampt

The pilot demonstrated the battery converter performance, in particular item 1 above, as well as the architecture itself. Please see attached pilot data.

A five-second trace showing the DC bus voltage near 800 V while current alternates between zero and full load.
In the five-second customer pilot trace, bus voltage stays close to 800 V while the emulated GPU load switches between zero and full load. Image supplied by Ampt.

What the pilot tells us

Ampt says the bus stayed within the limits it used for the zero-to-full-load test, equivalent to 680 V to 840 V on an 800 V bus. The converter’s current rise time, the size of the voltage excursion and the time it takes the rail to settle are three separate measurements. The supplied five-second chart shows how the bus behaved over repeated bursts. A closer view around a single step would show the initial voltage dip and the recovery to 800 V.

The written answers describe capacitors on both sides of the converter. On the battery side, they supply current while the battery responds and help hold up the converter’s input. On the rack side, they cover the fastest changes at the load while the converter’s output current is still rising. The battery carries the energy demand over the rest of the burst.

What the battery would have to supply

Take one 80 kW module and an illustrative load that spends equal time at zero and full power. Ignoring conversion and storage losses, that is a 40 kW average. A steady 40 kW upstream feed would leave the battery to supply the remaining 40 kW when the load is high, with the low-load interval available to recharge it. At that rate, a ten-second burst would draw 400 kJ, or about 0.11 kWh, from the battery before losses.

Ampt described how the upstream supply could ramp as demand rises. At a site already at its connection limit, a longer sequence of high loads can leave the battery with too little time to recharge. Sizing then depends on the duration and spacing of the peaks as well as the size of the power shortfall.

Ampt has the converter in partner pilots and is targeting general availability in the third quarter of 2027.