Explainer

What a fuse’s I²t rating tells you about a DC fault

Melting I²t describes the first part of an interruption, while total clearing I²t includes the current that continues through the arc.
A 100 A fuse next to its open holder

Image: Zureks · CC BY 3.0

When a fuse element melts during a DC fault, current can keep flowing through the arc until the fuse finishes interrupting it. That is why a datasheet may show two I²t values for the same part: one for melting the element and another for the whole interruption. A component in the fault path carries current through both stages.

Follow the current until it stops

I²t is the time integral of current squared, in ampere squared seconds. A constant 100 A pulse lasting 2 ms gives 100² × 0.002 = 20 A²s. That shortcut only works for a flat pulse because fault current varies as the fuse operates. For a 10 mΩ path with constant resistance, 20 A²s would deposit 0.2 J as heat. The resistance and the device’s transient thermal behaviour determine what that figure means for semiconductor junction temperature.

Melting I²t ends when the fuse element opens and an arc forms. Add the current-squared integral during that arcing interval to get total clearing I²t. The size of the second term depends on the circuit and the fuse. For a DC system, match the data to the available voltage, prospective fault current and, where specified, the circuit’s L/R time constant. A fuse’s DC interrupting rating is a separate limit: the fuse must be able to interrupt the available fault at the circuit voltage.

Treat startup and fault protection as separate checks

During startup, compare the inrush waveform with the manufacturer’s pulse withstand and derating guidance. A pulse that is harmless on one start may shorten the fuse’s life when it repeats. For a high-current fault, compare the fuse’s total clearing data with the downstream component’s limits at comparable conditions. That can mean transient thermal impedance or a safe operating area curve for a semiconductor, rather than a single I²t figure. A long, modest overload calls for the time-current curve, where heat has more time to escape from the element than during a short surge.

A datasheet that gives only a nominal melting value leaves the interruption comparison incomplete. Ask for DC clearing data for the actual fuse and applicable conditions before making that comparison.

A 100 A fuse next to its open holder. Resized for web; no crop.

Sources: Littelfuse: Fuseology selection guide; Eaton Bussmann: high-speed fuse application guide.

Continue reading